The Freezer Read 70 Degrees: What a Hacked Köniz Cold Room Teaches Every Building
A Köniz butcher's freezer read 50 to 70 °C after its cooling control was manipulated. What Swiss planners should specify for every networked BACS point.
The number on the display belonged on an oven. In early November, the owner of Lüthi’s Fleischwaren in Köniz BE told SRF on 5 November that the shop’s freezer had measured «50 bis 70 Grad», 50 to 70 °C where minus 18 °C was expected. Someone had manipulated the electronic control of the cooling and freezer plant. According to Keystone-SDA on 6 November, the meat was practically cooked and the price tags had melted. A freezer at 70 °C is, technically, a slow cooker.
The laugh belongs to the system, never to the shop. A small butcher did nothing unusual here. They ran a networked cooling plant, as many shops do, and they informed their customers on 5 November. The plant was taken off the network and the shop closed for now. Reopening is planned for about 20 November, once the cooling runs reliably again. We wish them a full counter and a cold freezer.
They were not alone. Volg confirmed to SRF that three of its shops found changed parameters on chiller shelves. Blick reporters Sara Belgeri and Anna Clara Kohler reported on 7 November that Migros, Lidl Schweiz and Coop saw no successful attacks, though Coop confirmed failed attempts. Across Europe the pattern was wider: Al Jazeera reported that attackers heated fridges and freezers in hundreds of French supermarkets to as high as 50 °C in October, and that a second wave from 2 November made shops run hot in several European countries. Kantonspolizei Bern was informed, and perpetrators and motive are still unknown.
A cold room is now a computer with a compressor
What is a cold room in 2026? A compressor, a set of sensors, and a networked controller with a login screen. The attack broke no metal and cut no pipe. It changed a setpoint. That is the whole essence of the story: the physical plant did exactly what its controller told it, faithfully and well.
Marc Ruef, co-founder of Scip AG, told Blick that attackers usually walk in through unchanged default accounts or weak passwords, and that the weak point is the networking itself: «Nicht jedes Gerät sollte ans Internet gehängt werden – auch wenn es technisch möglich wäre.» He also noted that the number of published vulnerabilities has risen fourfold (4×) since January. Blick, citing the Bundesamt für Cybersicherheit (BACS), counts 222 attacks on critical infrastructure in 2025; a reporting duty for operators has applied since 1 April 2025.
The Swiss bakers’ association SBC put the fix plainly on 11 November: «Online-Zugänge zu Kältesteuerungen dürfen niemals offen über das Internet erreichbar sein.» Its list is short and adult: VPN-only remote access, individual strong passwords, read-only where nobody needs to write, updates checked with the manufacturer and the refrigeration planner, and a manual temperature log as the emergency plan.
←TODAY: A Bernese freezer showed 50–70 °C because a controller accepted a changed setpoint from the network. →3012: Zurich’s buildings run on thousands of small brains, each with a named keeper. Fulcrum: Remote access is a door you specify in the tender, not a feature you switch on later.
Every building-automation point is a door
Now look at your own building. Heat pump, air-handling unit, blinds, cold storage, the lift’s remote diagnostics: each Gebäudeautomation point a planner networked for convenience is also an entry. NIST SP 800-207, the 2020 zero-trust reference by Rose, Borchert, Mitchell and Connelly, says there is no trusted inside, only the next request and whether it can prove itself. A heat pump controller on a public IP with the factory password has proven nothing. Convenience for the service technician and exposure to the whole internet arrive through the same port.
From where I sit, the plants that aged badly were the ones nobody could still administer after the integrator left. The quiet heroes of this story are the refrigeration technicians now restoring the affected plants, and the people writing temperature logs by hand. Give them a list to work from.
Atelier: An office specifying building automation is also specifying who can open each door, usually without writing it down. When the Leistungsverzeichnis says «Fernzugriff», the tender rarely names a VPN, a password policy or an owner. Monday move: add one line to your building-automation specification template requiring VPN-only remote access, changed credentials at handover, and a named responsible person per controller.
Hack: Pull every risky controller out of your project’s device inventory with one query. Keep a simple table per building, filled from the integrator’s handover list, and ask it the three SBC questions at once. Anything this query returns needs a decision before handover.
SELECT building, device, system, ip_address
FROM bacs_controllers
WHERE (internet_reachable = TRUE AND via_vpn = FALSE)
OR password_changed = FALSE
OR owner_name IS NULL;If you want that inventory to live next to the model instead of in a spreadsheet, the PAZ Academy Archicad Python Automatisierung course shows how to write device properties into Archicad objects and export them with a script. Factory passwords: the one thing in the shop nobody chilled.
Open your building’s controller list, run the query, and put a name next to every door.
PAZ Kaffi · multidisciplinary editorial, led by PAZ Academy